Basler Electric BE1-851 Modbus Protocol User Manual
Page 59

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-21
47437
Today's Peak Demand Timestamp - Day
INT
47442
Today's Peak Demand Timestamp - Day
INT
47447
Today's Peak Demand Timestamp - Day
INT
47452
Today's Peak Demand Timestamp - Day
INT
47457
Today's Peak Demand Timestamp - Day
INT
Read
only:
Any value (days since 01/01/1984).
47438-39
Today's Peak Demand Timestamp - Millisecond
LI
47443-44
Today's Peak Demand Timestamp - Millisecond
LI
47448-49
Today's Peak Demand Timestamp - Millisecond
LI
47453-54
Today's Peak Demand Timestamp - Millisecond
LI
47458-59
Today's Peak Demand Timestamp - Millisecond
LI
Read
only:
0
to
86,399,999
milliseconds.
47460-61
Peak Since Reset Demand Current - Phase A
FP
47465-66
Peak Since Reset Demand Current - Phase B
FP
47470-71
Peak Since Reset Demand Current - Phase C
FP
47475-76
Peak Since Reset Demand Current - Neutral
FP
47480-81
Peak Since Reset Demand Current - Neg-Seq
FP
Read only:
Any value (amps)
47462
Peak Since Reset Demand Timestamp - Day
INT
47467
Peak Since Reset Demand Timestamp - Day
INT
47472
Peak Since Reset Demand Timestamp - Day
INT
47477
Peak Since Reset Demand Timestamp - Day
INT
47482
Peak Since Reset Demand Timestamp - Day
INT
Read only:
Any value (days since 01/01/1984).
47463-64
Peak Since Reset Demand Timestamp - Millisecond
LI
47468-69
Peak Since Reset Demand Timestamp - Millisecond
LI
47473-74
Peak Since Reset Demand Timestamp - Millisecond
LI
47478-79
Peak Since Reset Demand Timestamp - Millisecond
LI
47483-84
Peak Since Reset Demand Timestamp - Millisecond
LI
47486
Reset
Logic
Alarm
Information
SI
47487
Reset
Major
Alarm
Information
SI
47488
Reset
Minor
Alarm
Information
SI
47489
Reset
Relay
Alarm
Information
SI
47491
Clear
Fault
Log
SI
47492
Trigger Fault Record
SI
47493
Clear
Events
Report
SI
Read:
0
Write:
Any value will perform reset / trigger / clear.
47512
Fault
Indicator
SI
Read
only:
Most recent fault number (1 - 255)
47513
Fault
Template
Status
SI
Read
only:
0: Template not valid for current Fault Selection
(Refer to Register 40038). All FLT template values will read 0.
1 to 255: Valid user selected fault number.