Global parameters, Control parameters – Basler Electric BE1-851 Modbus Protocol User Manual
Page 43

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-5
Note: Write to Report Selection and Report Focus to specify the report, which will be
made available via the Report (RPT) Template. The template is the Report Text Block at
47595-719.
Table 3-1. Report
Report Text
47595-719
Report Selection
40039
Report Focus
40040
RA-LGC Report
1
Not used
RA-MAJ Report
2
Not used
RA-MIN Report
3
Not used
RA-REL Report
4
Not used
RF Report
7
Not used
RF-# Report
8
Value of # (1 - 255)
RF-NEW Report
9
Not used
RS Report
10
Not used
RS-# Report
11
Value of # (1 - 255)
RS-NEW Report
12
Not used
RS-F# Report
13
Value of # (1 - 255)
Global Parameters
Global Parameter registers 40080 - 40099 are only for serial communication ports active with ASCII
protocol and for the Modbus
™ serial port, COM2, when Password Security register 40989 is enabled.
40080-83
Global
Password ASC(8)
40085-88
Setting
Password
ASC(8)
40090-93
Control
Password
ASC(8)
40095-98
Report
Password
ASC(8)
Read: If global access granted, password ASCII characters are read. Otherwise, the
ASCII character “
∗” is read.
Write: Password in ASCII character(s).
Note: If password written is less than 8 characters long, a binary zero value must be
included following the final password character.
40084
Global
Path
BM(8)
40089
Setting Path
BM(8)
40094
Control Path
BM(8)
40099
Report Path
BM(8)
Read: Path associated with password.
Write: Path associated with password.
Bit 2 is set for COM 2 access.
Bit 1 is set for COM 1 access.
Bit 0 is set for COM 0 / FP access.
Control Parameters
All values read from and written to Select and Operate registers are ASCII characters. Select registers
must be written first, followed by a write to the Operate register. A 30 second window starts after the first
write to the Select register. If the second write to the Operate register is not received within the 30-second
window, an error response will be returned.
Writes to Operate registers 40138, 40140 - 40150 with ASCII data ‘E‘ (Enable Output override control) or
‘D’ (Disable Output override control) requires an additional write of ‘Y’ to Exit register 40001 to allow these
control settings to be saved to the relay’s internal EEPROM.
NOTE
Do not use Control Parameter Registers interchangeably with the Legacy Control
Registers.