Basler Electric BE1-851 Modbus Protocol User Manual
Page 58

3-20 BE1-851
Modbus
™ Protocol
9289900992 Rev F
47389-92
Current
Active
Logic
Scheme
ASC(8)
Read
Only:
Current active logic name.
47393
Reclose
Status
Read
only:
0
for
Off
1 for Timing reclose #1
2 for Timing reclose #2
3 for Timing reclose #3
4 for Timing reclose #4
5
for
Wait
6
for
Lockout
7
for
Reset
8
for
Timing
fail
9
for
Timing
reset
47394-95
Breaker Contact Duty Log - Phase A
FP
47396-97
Breaker Contact Duty Log - Phase B
FP
47398-99
Breaker Contact Duty Log - Phase C
FP
Read:
If Breaker Duty Type = Off or Maximum Breaker Duty = 0, reads undefined
floating point value of 0xFFFFFFFF. Otherwise, reads 0.00 to 200.00%.
Write:
0
to
200%
47400-01
Breaker
Operations
Counter
LI
Read
and
Write:
0 to 99,999
47410-11
Yesterday's Peak Demand Current - Phase A
FP
47415-16
Yesterday's Peak Demand Current - Phase B
FP
47420-21
Yesterday's Peak Demand Current - Phase C
FP
47425-26
Yesterday's Peak Demand Current - Neutral
FP
47430-31
Yesterday's Peak Demand Current - Neg-Seq
FP
Read only:
Any value (amps)
47412
Yesterday's Peak Demand Timestamp - Day
INT
47417
Yesterday's Peak Demand Timestamp - Day
INT
47422
Yesterday's Peak Demand Timestamp - Day
INT
47427
Yesterday's Peak Demand Timestamp - Day
INT
47432
Yesterday's Peak Demand Timestamp - Day
INT
Read
only:
Any value (days since 01/01/1984).
47413-14
Yesterday's Peak Demand Timestamp - Millisecond
LI
47418-19
Yesterday's Peak Demand Timestamp - Millisecond
LI
47423-24
Yesterday's Peak Demand Timestamp - Millisecond
LI
47428-29
Yesterday's Peak Demand Timestamp - Millisecond
LI
47433-34
Yesterday's Peak Demand Timestamp - Millisecond
LI
Read
only:
0
to
86,399,999
milliseconds.
47435-36
Today's Peak Demand Current - Phase A
FP
47440-41
Today's Peak Demand Current - Phase B
FP
47445-46
Today's Peak Demand Current - Phase C
FP
47450-51
Today's Peak Demand Current - Neutral
FP
47455-56
Today's Peak Demand Current - Neg-Seq
FP
Read only:
Any value (amps)