Basler Electric BE1-851 Modbus Protocol User Manual
Page 57

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-19
47383
Active
Alarm
Flags
(ProgAlarms)
LSBs
BM(16)
Read Only:
Bit 15 - User settings changed, (‘EXIT’ with ‘Y’)
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Excessive unbalance alarm, 50TQ unbalance output picked up
Bit 8 - Neutral demand alarm, neutral demand maximum exceeded
Bit 7 - Phase demand alarm, phase demand maximum exceeded
Bit 6 - Breaker alarm #3
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Recloser lockout alarm
Bit 2 - Recloser fail alarm
Bit 1 - Breaker fail alarm
Bit 0 - Trip Circuit Monitor alarm
47384
Target
Status
MSBs
BM(16)
Read:
Bit 15 - BF
Bit 14 - 162
Bit 13 - 62
Bit 12 - 50TQ (250TN, Sensing input “G”)
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ (350TN, Sensing input “G”)
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA
Write: Any value to either register to reset all.
47385
Target
Status
LSBs
BM(16)
Read:
Bit 15 - Spare
Bit 14 - 362
∗
Bit 13 - 262
∗
Bit 12 - 51Q (151N, Sensing input “G”)
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
Bits 7-0 - Spare
Write: Any value to either register to reset all.
∗ 262 and 362 are available when style option 1 is V or W.
47388
Current
Breaker
Status
ASC(1)
Read
only:
O
for
Open
C for Closed
D for Disabled (off)