Basler Electric BE1-851 Modbus Protocol User Manual
Page 44

3-6 BE1-851
Modbus
™ Protocol
9289900992 Rev F
40117
Select Group
ASC(1)
Read: To read a value other than ASCII character ‘X’, the Select Group register must be
the most recent control register written AND must have been written within the previous
30 seconds.
0 if Group 0 selection has been made.
1 if Group 1 selection has been made.
2 if Group 2 selection has been made.
3 if Group 3 selection has been made.
L if Logic selection has been made.
X if Group control not selected or control timer has expired
Write: the desired ASCII character.
0 to select Group 0.
1 to select Group 1.
2 to select Group 2.
3 to select Group 3.
L to select Logic.
40118
Operate
Group
ASC(1)
Read: Current control.
0 if Group 0.
1 if Group 1.
2 if Group 2.
3 if Group 3.
L if Logic.
Write: the desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).
0 to select Group 0.
1 to select Group 1.
2 to select Group 2.
3 to select Group 3.
L to select Logic.
40119
Select Virtual Selector Switch 43
ASC(1)
40121
Select Virtual Selector
Switch
143
ASC(1)
40123
Select Virtual Selector Switch 243 †
ASC(1)
40125
Select Virtual Selector Switch 343 †
ASC(1)
Read: To read a value other than ASCII character ‘X’, the Select Virtual Selector Switch
register must be the most recent control register written AND must have been written
within the previous 30 seconds.
P if Pulse Switch selection has been made.
0 if Latch Switch at 0 selection has been made.
1 if Latch Switch at 1 selection has been made.
X if Virtual Selector Switch control not selected or control timer has expired.
Write: The desired ASCII character.
P to select Pulsing the Switch.
0 to select Latching the Switch at 0.
1 to select Latching the Switch at 1.
40120
Operate Virtual Selector Switch 43
ASC(1)
40122
Operate Virtual Selector Switch 143
ASC(1)
40124
Operate Virtual Selector Switch 243 †
ASC(1)
40126
Operate Virtual Selector Switch 343 †
ASC(1)
Read: Current control.
P if Pulse Switch.
0 if Latch Switch at 0.
1 if Latch Switch at 1.
Write: The desired ASCII character to alter control (corresponding Select register must
contain same value, written within previous 30 seconds).
P to Pulse Switch.
0 to Latch Switch at 0.
1 to Latch Switch at 1.