Basler Electric BE1-851 Modbus Protocol User Manual
Page 54

3-16 BE1-851
Modbus
™ Protocol
9289900992 Rev F
47296-302
Boot SW Version # / Date
ASC(14)
47310-16
Serial
Number
ASC(13)
47324-34
Style
Number
ASC(21)
Read
Only:
ASCII strings
47364
Date
and
Time
-
Day
INT
Read
and
Write:
Any value (days since 01/01/1984)
47365-66
Date and Time - milliseconds
LI
Read
and
Write:
0 to 86,399,999 milliseconds
47367
System Status (Logic Var 0 to 15)
BM(16)
Read
only:
Bit 15 - 150TQ picked-up (350TN, Sensing input “G”)
Bit 14 - 50TQ picked-up (250TN, Sensing input “G”)
Bit 13 - 150NT picked-up
Bit 12 - 50TN picked-up
Bit 11 - 150PT picked-up
Bit 10 - 50TP picked-up
Bit 9 - 51Q tripped (151N, Sensing input “G”)
Bit 8 - 51N tripped
Bit 7 - 51P tripped
Bit 6 - BF tripped
Bit 5 - 150TQ tripped (350TN, Sensing input “G”)
Bit 4 - 50TQ tripped (250TN, Sensing input “G”)
Bit 3 - 150TN tripped
Bit 2 - 50TN tripped
Bit 1 - 150TP tripped
Bit 0 - 50TP tripped
47368
System Status (Logic Var 16 to 31)
BM(16)
Read
only:
Bit 15 - Logic always false
Bit 14 - 79 block output
Bit 13 - 79 reclose fail
Bit 12 - 79 lockout
Bit 11 - 79 enable / active / block tap changer
Bit 10 - 79 close
Bit 9 - Serial controlled switch 343 (Serial controlled switch 143
∗)
Bit 8 - Serial controlled switch 243 (Serial controlled switch 43
∗)
Bit 7 - Serial controlled switch 143 (362 tripped
∗)
Bit 6 - Serial controlled switch 43 (262 tripped
∗)
Bit 5 - 162 tripped
Bit 4 - 62 tripped
Bit 3 - 51Q picked-up (151N, Sensing input “G”)
Bit 2 - 51N picked-up
Bit 1 - 51P picked-up
Bit 0 - BF picked-up
∗ Used when style option 1 is V or W.
47369
System Status (Logic Var 32 to 47)
BM(16)
Read
only:
Bit 15 - Virtual Output 15 status
Bit 14 - Virtual Output 14 status
Bit 13 - Virtual Output 13 status
Bit 12 - Virtual Output 12 status
Bit 11 - Virtual Output 11 status