System data setting parameters, Breaker duty setting parameters, Relay data setting parameters – Basler Electric BE1-851 Modbus Protocol User Manual
Page 50

3-12 BE1-851
Modbus
™ Protocol
9289900992 Rev F
† When Password Security in enabled, relay parameters can be changed via Modbus
™ only if access is
obtained via the Access Password and Access Request holding registers, and released via the Exit
register with value 89 (ASCII character “Y”).
System Data Setting Parameters
41019
System
Frequency
SI
Read
and
Write:
50 for 50 hertz
60 for 60 hertz
41020
Phase
Rotation
SI
Read
and
Write:
1 for ABC rotation
2 for ACB rotation
41021
Phase
CT
Ratio
INT
41022
Neutral
CT
Ratio INT
Read
and
Write:
1 to 50,000
Breaker Duty Setting Parameters
41092
Breaker
Duty
Type
FP
Read
and
Write:
0
for
Off
1 for Sum I, primary centi-amps
2 for Sum I
2
, primary centi-amps
41093-94
Maximum
Breaker
Duty
FP
Read
and
Write:
0
to
4.29E+09
amps
41096
Programmable Breaker Alarm #1 Mode
INT
41099
Programmable Breaker Alarm #2 Mode
INT
41102
Programmable Breaker Alarm #3 Mode
INT
Read and Write:
0
for
Disabled
1
for
Percent
duty
2 for Breaker operations
3 for Clearing time
41097-98
Programmable Breaker Alarm #1 Limit
FP
41100-01
Programmable Breaker Alarm #2 Limit
FP
41103-04
Programmable Breaker Alarm #3 Limit
FP
Read
and
Write:
If mode is 0: Reads 0, any value writes 0
If mode is 1: 0.00 to 100.00%
If mode is 2: 0 to 99,999
If mode is 3: 0, 20 to 1000 milliseconds
Relay Data Setting Parameters
41259-60
Phase
Demand
Alarm
Level
FP
41261-62
Neutral
Demand
Alarm
Level
FP
41263-64
Negative-Sequence Demand Alarm Level
FP
Read
and
Write:
0 to 16.0 amps
41265
Major
Alarm
Mask
MSBs BM(16)
41267
Minor
Alarm
Mask
MSBs BM(16)
41269
Logic
Alarm
Mask
MSBs BM(16)