3-22 BE1-851
Modbus
™ Protocol
9289900992 Rev F
Fault Template (FLT)
47514
Fault Date and Time - Day
INT
Read
only:
Any value (days since 01/01/1984).
47515-16
Fault Date and Time - Milliseconds
LI
Read
only:
0 to 86,399,999 milliseconds
47517
Fault
Event
Type BM(16)
Read
only:
Bit 0 for Breaker Fail
Bit 1 for Trip
Bit 2 for Logic
Bit 3 for Pickup
Bit 4 for Fault Record Trigger (Refer to Register 47492)
47518
Fault
Active
Group
SI
Read
only:
0 to 3
47519
Fault
Targets
MSBs
BM(16)
Read
only:
Bit 15 - BF
Bit 14 - 162
Bit 13 - 62
Bit 12 - 50TQ (250TN, Sensing input “G”)
Bit 11 - 50TN
Bit 10 - 50TC
Bit 9 - 50TB
Bit 8 - 50TA
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Spare
Bit 4 - 150TQ (350TN, Sensing input “G”)
Bit 3 - 150TN
Bit 2 - 150TC
Bit 1 - 150TB
Bit 0 - 150TA
47520
Fault
Targets
LSBs
BM(16)
Read
only:
Bit 15 - Spare
Bit 14 - 362
∗
Bit 13 - 262
∗
Bit 12 - 51Q (151N, Sensing input “G”)
Bit 11 - 51N
Bit 10 - 51C
Bit 9 - 51B
Bit 8 - 51A
BitS 7-0 - Spare
∗ 262 and 362 are available when style option 1 is V or W.
47524
Fault
Clearing
Time
Status
SI
Read
only:
0 if Valid Fault Clearing Time (Registers 47525-26) value
1 if No pickup
2 if N/A; Out of range