Basler Electric BE1-851 Modbus Protocol User Manual
Page 51

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-13
Read
and
Write:
Bits 15 to 10 - Spare
Bit 9 - Changes Lost alarm
Bit 8 - Logic=None alarm
Bit 7 - Fault Record Time Out
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non-fatal error
41266
Major
Alarm
Mask
LSBs
BM(16)
41268
Minor
Alarm
Mask
LSBs
BM(16)
41270
Logic Alarm Mask LSBs
BM(16)
Read only:
Bit 15 - User settings changed, (‘EXIT’ with ‘Y’)
Bit 14 - Power reset alarm, hard reset of MPU
Bit 13 - Clock problem, real time clock has not been set
Bit 12 - Communicating failure alarm, read error on serial port
Bit 11 - Operating System Overload detected alarm
Bit 10 - Setting group override in effect
Bit 9 - Q demand alarm, excessive negative-sequence unbalance
Bit 8 - Neutral demand alarm
Bit 7 - Phase demand alarm
Bit 6 - Breaker alarm #3
Bit 5 - Breaker alarm #2
Bit 4 - Breaker alarm #1
Bit 3 - Recloser lockout alarm
Bit 2 - Recloser fail alarm
Bit 1 - Breaker fail alarm
Bit 0 - Trip Circuit Monitor alarm
41272
Clock
Format
-
Date
ASC(1)
Read
and
Write:
M for mm/dd/yy format
D for dd/mm/yy format
41273
Clock Format - Time
SI
Read
and
Write:
12 for 12 hour clock
24 for 24 hour clock
41274
Clock
Format
-
Daylight
Savings
SI
Read
and
Write:
0 for disabling Daylight Savings
1 for enabling Daylight Savings
41275
Phase
Demand
Interval
SI
41276
Neutral
Demand
Interval SI
41277
Negative-Sequence
Demand
Interval
SI
Read
and
Write:
1 to 60 minutes
0
to
disable
41284
Output
Hold
Mask
BM(8)
Read
and
Write:
Bit 7 - Spare
Bit 6 - Spare
Bit 5 - Output 5 Status