6. Control and settings through the Internet

Double click the IP address in IPEDIT and you can enter the login web page. Input the default
password 12345678 (you can change the password after log in), click the OK and then you can
enter the Web Control page.

Username: admin / Password: 12345678














Sensor of IP Power 9212: Read IO

Source mode (Voltage input):
IN1-IN4 contacts are active signal sensors. If the voltage difference between the two contacts in
one set within 0V~3V, 9212 shows ON. It the voltage difference within 4V~24V, 9212 shows
OFF. So user can detect the change of equipment. Such as smoke detector, light detector and
gas detector.

Sink mode (Resistance Input):

IN5-IN8 contacts are short circuit sensors. If the resistance between the two contacts in one set
within

0Ω~200Ω, 9212 shows ON. If the resistance within 500Ω~

∞,

9212 shows OFF. So user

can detect the movement of equipment through the magnetic reed switch or other kind of
reactive sensors.

NOTE:
1. The data in this figure is the average measure value. To ensure the correct detection, we
suggest user set the voltage lower than

200Ω when it shows ON and higher than 500Ω when it

shows OFF.