Section 5. calibration, Calibration setup, Service environment and precautions – AMETEK XHR 1000 Watt Series User Manual

Page 75: Equipment required

background image

75

Section 5. Calibration

Calibration Setup

Service

Environment

and

Precautions

Follow established antistatic procedures.

Work at a bench with adequate room and support for the test unit and for all

equipment required.

To reduce shock hazard, use only an insulated, straight-bladed screwdriver when

calibrating trim potentiometers.

NEVER test these units alone. Ensure that someone is present who can help

should an accident occur.

Equipment

Required

You will need the following equipment when calibrating your supply.

5-1/2 digit true RMS voltmeters (DVMs) (±0.05% accuracy) with test leads.

Current shunt 1 mV/amp (±0.25%) and connecting wire. Current rating for the

DC shunt and connecting wire must be at least 10% greater than the power

supply’s output current rating. See also Table 2.3, “Current Carrying Capacity

for Wiring”.

Non-conducting, straight-bladed screwdriver.

WARNING- HIGH ENERGY AND HIGH VOLTAGE
Exercise caution when using and servicing a power supply. High energy levels
can be stored at the output voltage terminals on a power supply in normal
operation. In addition, potentially lethal voltages exist in the primary circuit and
on the output and sense connectors of a power supply with a rated output
greater than 40 V. Filter capacitors store potentially dangerous energy for some
time after power is removed.