Load Connection

40

Operating Manual for XHR Series Power Supply

Load Wiring Length for Operation with Sense Lines

For applications using

remote sensing, you must limit the voltage drop across each load line.

Figure 2.2

shows some maximum allowable wire lengths for a given load current and wire size.
We recommend that you use the larger load wiring to ensure a smaller voltage drop
(1 V typical maximum), although the units (except 7.5 V models) will compensate
for up to 5 V drop in each line. See also

“Local and Remote Sensing” on page 48

.

Figure 2.2 Maximum Load Wire Length for 1 V Line Drop

Noise and Impedance Effects

To minimize noise pickup and radiation, use

shielded pair wiring of shortest possible length for load wires. Connect the shield to
the chassis using the ground screw on the rear panel. Where shielding is impossible
or impractical, simply twisting the wires together will offer some noise immunity.
When using local sense connections, use the largest practical wire size to minimize
the effects of load line impedance on the regulation of the supply.