Remote Monitoring of Output Voltage and Current

TM-F2OP-C1XN-01

4-7

Remote Monitoring of Output Voltage and Current

Readback Signals

The J2 connector on the rear panel provides access to calibrated readback
signals for remote monitoring of the output voltage and current. Rear
panel switches SW1-5 and SW1-6 allow you to select either a 0-5 Vdc or
a 0-10 Vdc range for the output. The readback signal represents 0 to
100% of the power supply’s output.

See Table 4-1

for the required J2 connections and switch settings for

remote monitoring of readback signals with 0-5 Vdc or 0-10 Vdc outputs.
Use shielded pair wiring (20 to 24 AWG) and ground the shield to J10
sense connector terminal 1 (return sense) or to the chassis.

Note: Check the readback accuracy any time you reset switches SW1-5
and SW1-6. See Chapter 5.

Table 4-3 Settings for Remote Monitoring of Readback Signals

Readback Signal

J2 Connection
Signal (+)

J2 Connection
Return (–)

Switch SW1 Setting

Output Voltage
(0-5 Vdc)

J2-10

J2-9

SW1-5 OFF
(OPEN)

Output Voltage
(0-10 Vdc)

J2-10

J2-9

SW1-5 ON
(CLOSED)

Output Current
(0-5 Vdc)

J2-12

J2-11

SW1-6 OFF
(OPEN)

Output Current
(0-10 Vdc)

J2-12

J2-11

SW1-6 ON
(CLOSED)