beautypg.com

Load wiring length for operation with sense lines, Figure 2-3, Maximum load wire length for 1 v line drop –13 – AMETEK XFR 2800 Watt Series User Manual

Page 41: Table 2-4, Current carrying capacity for load wiring –13

background image

Load Connection

TM-F2OP-C1XN-01

2-13

Load Wiring Length for Operation with Sense Lines

For applications using remote sensing, you must limit the voltage drop
across each load wire. Figure 2-3

shows some allowable wire lengths for

a given load current and wire size. We recommend that you use the larger
load wiring to ensure a smaller voltage drop (1 V typical maximum),
although units will compensate for up to 5 V drop in each line. See also
“Local and Remote Sensing” on page 2–21.

)

Table 2-4 Current Carrying Capacity for Load Wiring

Wire Size
(AWG)

Maximum Current (A)

Wire Size
(AWG)

Maximum Current (A)

20

2.5

6

61

18

4

4

97

16

6

2

155

14

10

1

192

12

16

1/0

247

10

21

2/0

303

8

36

Figure 2-3 Maximum Load Wire Length for 1 V Line Drop

WIRE GAUGE (AWG)

16

14

12

10

8

6

4

2

1/0

1

2/0

WIRE LENGTH (FEET)

100

90

80

70

60

50

40

30

20

10

LOAD CURRENT (AMPS)

1

2

3

4

5

6 7

8

9 10

20

30

40

50

60

70 80 90 100

200

300

400

500