beautypg.com

Sensing for parallel operation, Sensing for parallel operation –14, Figure 3-3 – AMETEK XFR 2800 Watt Series User Manual

Page 66: Parallel operation of multiple supplies –14

background image

Local Operation

3-14

TM-F2OP-C1XN-01

Sensing for Parallel Operation

Use default local sensing to enhance power sharing between units, as the
impedance of the load lines will tend to correct for current imbalance. If
you use remote sensing at the load for better voltage regulation, one
supply always operates in current limit mode and supplies most of the
power.

Figure 3-3 Parallel Operation of Multiple Supplies

(Local sense lines shown are default J10 connections.)