Cyclone HUSH enclosures must be provided with an exhaust duct for exhaust air, from the top of

the enclosure to a location where the noise of the Cyclone fans will not be heard. This is usually

an insulated ceiling void, drop ceiling, an adjoining room, or an outside wall.

The exhaust duct is normally installed by an air conditioning installer, and rated for airflow as

follows:

Cyclone 8000, 8100 HUSH

500cfm

0.25m

3

/s

Cyclone 8200 and up

1,000cfm

0.50m

3

/s

The Cyclone HUSH enclosure is supplied with a fan plate to be mounted at the far end of the duct.

Installer must provide a 3-conductor flexible cable rated at 250VAC, 10 Amps, conforming to local

electrical standards, to connect the fan plate to the Cyclone DEC controller, and pulled either

through the duct or in a separate electrical conduit.






Power and Signal

Conduit Entries