Appendix a: modbus map – CIRCUTOR CDP-0 User Manual
Page 71

CDP
Instruction Manual
71
APPENDIX A: MODBUS MAP
Note: All Modbus map addresses are shown in hexadecimal format.
Parameter
(3)(5)
Address
Units
Phase 1
Phase 2
Phase 3 Three-phase
Active power of the grid
(4)
64-65
66-67
68-69
6A-6B
kW
Active power measured in
the load
6C-6D
6E-6F
70-71
72-73
kW
Active photovoltaic power
74-75
76-77
78-79
7A-7B
kW
(3)
These parameters only accept the read function.
(4)
The sign indicates if it is consumed or generated.
(5)
Number of decimal places: 3
Parameter
(3)
Address
Units
Phase 1 Phase 2 Phase 3 Global
Regulation percentage
7D
7E
7F
7C
%
Parameter
(3)(6)
Address
Units
Active three-phase power measured in the load
80-81
kW·h
Active three-phase energy consumed from the grid
82-83
kW·h
Three-phase active photovoltaic energy consumed
84-85
kW·h
Active three-phase energy injected into the grid
86-87
kW·h
(6)
Number of decimal places: 3
Parameter
(3)
Address
Units
Channel 1 Channel 2 Channel 3
CDP measurement current
88
89
8A
A
Voltage measured in the CDP
(7)
8B
8C
8D
V
(7)
Number of decimal places: 1
Parameters
measured in
the load
(3)
Address
Units
Phase 1
Phase 2
Phase 3
Three-phase
Power Factor (PF)
(5)
8E-8F
90-91
92-93
94-95
-
Voltage THD
(7)
98-99
9A-9B
9C-9D
-
%
Current THD
(7)
9E-9F
A0-A1
A2-A3
-
%
Reactive power
(6)
A4-A5
A6-A7
A8-A9
-
kvar
Apparent power
(6)
AA-AB
AC-AD
AE-AF
-
kVA
Parameters measured in the load
(3)
Address
Units
Three-phase inductive reactive power
(6)
B0-B1
kvarL
Three-phase capacitive reactive power
(6)
B2-B3
kvarC
Three-phase apparent power
(6)
B4-B5
kVA
Frequency
(7)
96-97
Hz
L1-L2 voltage
(7)
B6-B7
V
L2-L3 voltage
(7)
B8-B9
V
L3-L1 voltage
(7)
BA-BB
V
Imported three-phase inductive energy
(6)
BC-BF
kvarLh
Imported three-phase capacitive energy
(6)
C0-C3
kvarCh
Imported three-phase apparent energy
(6)
C4-C7
kVAh
Exported three-phase inductive energy
(6)
C8-CB
kvarLh
Exported three-phase capacitive energy
(6)
CC-CF
kvarCh
Exported three-phase apparent energy
(6)
D0-D3
kVAh