3.5 Measured and recorded parameters
The parameters recorded by CIR-e³ can not be selected and they are those shown on the
following table. In case of measuring in a single phase circuit, only the parameters of phase L1
end energies are recorded. The rest of parameters are all zero.
Table 3-1.- List of measured and recorded parameters of CIR-e
3
Parameter
Symbol
L1
L2
L3
III
Max/ Min
Phase-neutral voltage
Vp-N
X
X
X
X
Phase-Phase voltage
Vp-p
X
X
X
X
Current
A
X
X
X
X
X
Neutral current (calculated)
AN
Frequency
Hz
X
X
Active Power (consumed)
kW
X
X
X
X
X
Reactive power L (consumed)
kvarL
X
X
X
X
X
Reactive power C (consumed)
kvarC
X
X
X
X
X
Apparent Power (consumed)
kVA
X
X
X
X
X
Power Factor *
PF
X
X
X
X
X
Cosinus *
Cos
X
X
X
X
X
Active Energy (consumed)
kW·h
X
Reactive Energy L (consumed)
kvar·h L
X
Reactive Energy C (consumed)
Kvar·h C
X
Apparent Energy
KVA·h
X
Maximum Demand Active P (Md)
kW (Md)
X
X
Maximum Demand Apparent Power
KVA (Md)
X
X
Harmonic decomposition V (50º)
Arm V
X
X
X
Harmonic decomposition A (50º)
Arm A
X
X
X
THD V
THD V
X
X
X
X
THD I
THD A
X
X
X
X
Fundamental V
X
X
X
Fundamental I
X
X
X
Flicker WA
WA
X
X
X
X
Flicker Pst
Pst
X
X
X
(*) The default value of angles is 1 when the analyzer doesn’t detect V and I.