6.1

General wiring guidelines

6

Wiring

6

6000

Wiring

Wiring

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

][Verdrahtung BA Einleitung

Please note:

][Verdrahtung ST ABS SSI

Use twisted pair cables to carry the differential signals (D+/D- and

Cl+/Cl-). This will increase the noise immunity.

Use shielded signal cables with metallic plugs.

On base modules with C-rail:

– Connect the shield to the terminals on the C-rail.

– Connect the C-rail with low impedance to the functional earth.

On base modules without C-rail:

– Connect the shield as shown in the terminal configuration section.

The module connects the shield to the mounting rail.

– Connect the mounting rail to the functional earth via an earthing

terminal.

The supply voltages must be extra low voltages with safe electrical

separation (PELV or SELV) in accordance with VDE 0100, Part 410.

Use copper wiring.

][Verdrahtung Zusatz mit C

The terminal configuration as stated on the front plate applies for base

modules with C-rail. The terminal configuration as stated in the tech-

nical documentation applies for all other base modules.

6.1.1

Mechanical connection of the base modules

Mechanical connection of the base modules

6-

][Modulverdrahtung mech

Procedure:

Use a flat blade screwdriver (DIN 5264-A)!

Strip the wire back 8 mm.

If necessary, label the connection level with a colour marker [3].

Base module with screw terminals:

– Use a screwdriver to loosen the screw on the screw terminal [1]

– Insert the stripped cable into the round fixing hole [2], as far as it

will go.

– Tighten up the screw on the screw terminal.

– Check that the cable is firmly seated.

DIN 5264-A