Configuration

4

Function description

4.2

Configuration

4200

Configuration

4-

4.2.1

Parameter

Parameter

4-

][Funktionsbeschreibung_BA_Zusatz Tabelle ABS SSI

The module has the following configuration options:

(1)

An error within the data frame means that the absolute encoder does

not terminate the serial data transfer with a zero.

Configuration

Default val-
ue

Key

Transmission rate

250 kHz

62.5 kHz
100 kHz
125 kHz
250 kHz
500 kHz
1 MHz
1.5 MHz

Gray code data format

On

On: Gray code is activated.
Off: Binary code is activated.

Fault detection within the data frame

(1)

On

On: Errors within the data frame are identified.
Off: Errors within the data frame are ignored.

Input data length

24

2 ... 32 Bit