Switch-on value
Switch-on value
4-
][Funktionsbeschreibung_BA_Konfig Einschalt ST-Aus 4xU
When the PSSuniversal is switched on, the output assumes the switch-
on value until the module receives data for the value of the output. You
can configure the outputs per channel with the manufacturer switch-on
value (default) or you can use a freely definable user switch-on value.
The manufacturer switch-on value is 0 V.
If the module does not receive any data from the module bus for 50 ms,
the outputs are reset to the switch-on value.
Switch-on values are entered in the system software as decimal vaues.
With default scaling, the decimal value (n) is calculated from the ana-
logue value at the output (U
Start
) as follows:
n = 32 767 * U
Start
/ 10 V
Example:
Switch-on values as an analogue value at the output (U
Start
):
– Switch-on value for channel 1 is to be 8 V.
– Switch-on value for channel 2 is to be 5 V.
Entry in the system software:
– Switch-on value 1 corresponds to 26 214
– Switch-on value 2 corresponds to 16 384
The relationship between the switch-on value and the actual voltage at
the output is dependent on the scaling. The module sets the voltage,
which corresponds to the switch-on voltage after scaling. Please refer
to the "Scaling" section in this manual.