Switch-on value

Switch-on value

4-

][Funktionsbeschreibung_BA_Konfig Einschalt ST-Aus 4xU

When the PSSuniversal is switched on, the output assumes the switch-

on value until the module receives data for the value of the output. You

can configure the outputs per channel with the manufacturer switch-on

value (default) or you can use a freely definable user switch-on value.

The manufacturer switch-on value is 0 V.

If the module does not receive any data from the module bus for 50 ms,

the outputs are reset to the switch-on value.

Switch-on values are entered in the system software as decimal vaues.

With default scaling, the decimal value (n) is calculated from the ana-

logue value at the output (U

Start

) as follows:

n = 32 767 * U

Start

/ 10 V

Example:

Switch-on values as an analogue value at the output (U

Start

):

– Switch-on value for channel 1 is to be 8 V.

– Switch-on value for channel 2 is to be 5 V.

Entry in the system software:

– Switch-on value 1 corresponds to 26 214

– Switch-on value 2 corresponds to 16 384

The relationship between the switch-on value and the actual voltage at

the output is dependent on the scaling. The module sets the voltage,

which corresponds to the switch-on voltage after scaling. Please refer