4.2

Configuration

4

Function description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-6

][Funktionsbeschreibung_BA_Konfig Skalier ST 4xU

Analogue value and typical digital value with a voltage range of
0 ... +10 V plus default values:

4.2.1.4

User scaling

User scaling

4-

][Funktionsbeschreibung_BA_Konfig Skalier Anwend Aus

User scaling is an additional scaling level prior to manufacturer scaling.

You can use this scaling to correct local influences. The function is the

same as that of manufacturer scaling:

y = (a

2

/ 256

D

* x) + b

2

or

y = (a

2

/ 100

H

* x) + b

2

a

2

= Amplification factor * 256

D

User scaling is deactivated in the default setting. The default value for

offset is 0. The default value for gain is 256

D

(100

H

). That corresponds

to amplification factor 1.

Analogue value of voltage

Hexadecimal digital value

Decimal digital value

0 V

0

0

5 V

4000

16 384

10 V

7FFF

32 767

5 V

6 V

7 V

8 V

9 V

4 V

3 V

2 V

1 V

0 V

10 V

32 767

29 490

26 214

22 937

19 660

16 384

13 107

9 830

6 553

3 277

0