Data formats, 4function description, 2 configuration – Pilz PSSu E S 4AO U User Manual
Page 24: 2 data formats

4.2
Configuration
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-8
4.2.2
Data formats
Data formats
4-
][Funktionsbeschreibung_BA_Konfig Format ST-Aus 4xU
The way in which the analogue value is displayed depends on the volt-
age range, on scaling and on the data format. The following examples
show the relationship between the values with default scaling.
You can configure the following data formats:
Two's complement (default)
The digital values are transferred with 15 bits plus a sign bit (MSB).
The MSB is "1" with negative values and "0" with positive values.
Sign and magnitude representation
The digital values are transferred with 15 bits plus a sign bit (MSB).
The MSB is "1" with negative values and "0" with positive values. With
negative values there is a distinction between sign and magnitude
representation and two's complement representation.
Formation of magnitude option
Negative digital values are converted into positive values of equal
magnitude.
As the module's resolution is 12 bits plus sign bit, the three least signif-
icant bits have no significance for the analogue value.
Analogue value and typical digital value, two's complement or sign
and magnitude representation:
Analogue value of voltage
Decimal digital value
Binary digital value
Hexadecimal digital value
0 V
0
0000 0000 0000 0000
0000
H
5 V
16 384
0100 0000 0000 0000
4000
H
10 V
32 767
0111 1111 1111 1111
7FFF
H