Wiring

Operating Manual PSSu K S 16DO 0.5
22059­EN­07

20

6

Wiring

6.1

General wiring guidelines

Please note:

}

The actuators may be connected using unshielded cables.

}

The outputs do not need suppression for inductive loads.

}

Use copper wiring.

6.1.1

Connectors' mechanical connection

Please note:

}

The conductor cross section on the spring­loaded terminals without ferrules is 0,20 ­
1,00 mm², 22 ­ 18 AWG.

}

If you are using multi­core or fine­core cables we recommend ferrules in accordance
with DIN 46228/Part 1 or DIN 46228/Part 4, 0.2 ... 1 mm

2

. To crimp the ferrules we re­

commend crimping pliers (crimp form A) conforming to EN 60947­1, such as the PZ 6/5
from Weidmüller, for example.

}

Terminal points per connection: 1

}

Stripping length: 8 mm

6.1.2

Connect/disconnect the cables

We recommend you use a screw driver with a 0.4 x 2.5 mm (DIN 5264) blade!

Strip the cable:

}

Strip the cable [1] and apply a ferrule if necessary (DIN 46228/Part 1 or DIN 46228/Part
4).

Connect cable:

}

Using the screwdriver, press the actuator button on the spring­loaded terminal down as
far as it will go [2], keep it held down and insert the stripped cable into the plug connec­
tion as far as it will go [2].

}

Check that the cable is firmly seated [3].

Disconnect cable:

}

Using the screwdriver, press the actuator button down as far as it will go [4], keep it
held down and pull the cable out of the plug connection [4].