Technical details
Operating Manual PSSu E S 4DI(T)
21340EN06
27
Inputs
312400
314400
Min. processing time of input when
signal changes from "1" to "0"
3,00 ms
3,00 ms
Min. processing time of input when
signal changes from "0" to "1"
3,00 ms
3,00 ms
Potential isolation between input
and internal module bus voltage
Yes
Yes
Environmental data
312400
314400
Climatic suitability
EN 6006821, EN 60068214, EN
6006822, EN 60068230, EN
60068278
EN 6006821, EN 60068214, EN
6006822, EN 60068230, EN
60068278
Ambient temperature
In accordance with the standard EN 60068214
EN 60068214
Temperature range
0 60 °C
40 70 °C
Storage temperature
In accordance with the standard EN 6006821/2
EN 6006821/2
Temperature range
25 70 °C
40 70 °C
Climatic suitability
In accordance with the standard EN 60068230, EN 60068278
EN 60068230, EN 60068278
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Shortterm
EMC
EN 6100042, EN 6100043, EN
6100044, EN 6100045, EN
6100046, EN 6100062, EN
6100064
EN 6100042, EN 6100043, EN
6100044, EN 6100045, EN
6100046, EN 6100062, EN
6100064
Vibration
In accordance with the standard EN 6006826
EN 6006826
Frequency
10,0 150,0 Hz
10,0 150,0 Hz
Amplitude
0,35 mm
0,35 mm
Acceleration
1g
1g
Broadband noise
In accordance with the standard –
EN 60068264
Frequency
–
5 500 Hz
Acceleration
–
1,9grms
Shock stress
In accordance with the standard EN 60068227
EN 60068227
Acceleration
15g
15g
Duration
11 ms
11 ms
In accordance with the standard EN 60068229
EN 60068229
Acceleration
10g
10g
Duration
16 ms
16 ms
Max. operating height above sea
level
–
5000 m
Airgap creepage
In accordance with the standard EN 606641
EN 606641
Overvoltage category
II
II
Pollution degree
2
2