7 operation, 1 messages, 2 display elements – Pilz PSSu E S 4DI User Manual
Page 24: 1 display elements for module diagnostics, Section 7, Operation, Messages, Display elements, Display elements for module diagnostics, 7operation

Operation
Operating Manual PSSu E S 4DI(T)
21340EN06
24
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"), sig
nalled to the head module and then entered in the head module's
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
The module can detect the following errors:
Module error
Explanation
Remedy
Startup error
Error as the PSSu system starts
up.
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry
does not match the actual hard
ware registry.
ST communication error
Error in ST communication with
the head module.
Change faulty module.
Bus termination error
There is no end bracket.
Install a terminating plate with in
tegrated end angle.
7.2
Display elements
Legend:
LED on
LED off
7.2.1
Display elements for module diagnostics
The module has an LED for displaying module errors ("Err" LED).
Err
11
I0
21
I1
Err
LED
Meaning
Name
Colour
Status
Err
No error
Red
Module error