6wiring, 2 terminal configuration – Pilz PSSu E AI SHT1 User Manual
Page 27

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-5
6.2
Terminal configuration
6
Wiring
Screw terminals:
PSSu BP 1/12S
PSSu BP 1/12S-T
Cage clamp terminals:
PSSu BP 1/12C
PSSu BP 1/12C-T
Without C-rail:
11: Output O0+
21: Output O1+
12: Output O0-
22: Output O1-
13-23: Shield connection
(13-23-16-26 linked within the base
module)
14: Input I0
24: 0 V analogue
15: Output O0-
25: Output O1-
16-26: Shield connection
(13-23-16-26 linked within the base
module)
Screw terminals:
PSSu BP-C 1/12S
PSSu BP-C 1/12S-T
Cage clamp terminals:
PSSu BP-C 1/12C
PSSu BP-C 1/12C-T
With C-rail:
11: Output O0+
21: Output O1+
12: Output O0-
22: Output O1-
13-23: C-rail supply,
shield connection
(13-23-16-26 linked within the base
module)
14: Input I0
24: 0 V analogue
15: Output O0-
25: Output O1-
16-26: C-rail supply,
shield connection
(13-23-16-26 linked within the base
module)
Base module
Terminal configuration
21
11
22
12
23
13
24
14
26
16
25
15
21
11
22
12
23
13
24
14
26
16
25
15