6 commissioning, 1 general wiring guidelines, 2 connecting the supply voltage – Pilz PNOZ m ES EtherCAT User Manual
Page 12: Section 6, Commissioning, General wiring guidelines, Connecting the supply voltage

Commissioning
Operating Manual PNOZ m ES EtherCAT
1003057-EN-01
12
Commissioning
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
It is possible to define which inputs and outputs on the safety system will communicate with
EtherCAT.
Note:
}
Information given in the "Technical details" must be followed.
}
Use copper wire that can withstand 75 °C.
Please note the following when connecting to EtherCAT:
}
The following minimum requirements of the connection cable and connector must be
met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45 connectors (indus-
trial connectors).
– 100BaseTX cable in accordance with the Ethernet standard (min. Category 5)
}
Measures to protect against interference:
Ensure the requirements for the industrial use of EtherCAT are met, as stated in the In-
stallation Manual published by the User Group.
ATTENTION!
Only connect and disconnect the expansion module when the supply volt-
age is switched off.
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
}
Terminal
24 V: + 24 V DC
}
Terminal
0 V: 0 V
6
6.1
6.2