Display elements, Display elements for device diagnostics, 7operation – Pilz PNOZ mc3p Profibus 2 User Manual
Page 24: 2 display elements, 1 display elements for device diagnostics

7.2
Display elements
7
Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-2
7.2
Display elements
7200
Display elements
7-
Anzeige Legende 3x
Legend:
7.2.1
Display elements for device diagnostics
Display elements for device diagnostics
7-
Betrieb_Anzeige_Feldbus_PROFIBUS-DP_BA
LED on
LED flashes
LED off
LED
Meaning
POWER
Supply voltage is present
Supply voltage is not present
ONLINE
PNOZ mc3p online, data exchange is possible
Master has sent the telegram "Global Control Clear". Virtual input bits i0 ... i23 are set
to "0"; expanded input bits i24 ... i127 are frozen.
PNOZ mc3p not online
OFFLINE
PNOZ mc3p offline, data exchange is not possible
PNOZ mc3p not offline
FAULT
Application Watchdog Timeout
1 Hz
Configuration error, length of input and/or output data during initialisation of the
PNOZ mc3p does not match the configuration
Remedy:
Ensure that the right GSD file has been used.
2 Hz
Configuration error, length/contents of configuration data during initialisation of the
PNOZ mc3p does not match the configuration
Remedy:
Ensure that the right GSD file has been used.
4 Hz
Error when initialising PROFIBUS-DP
No error