7.2

Display elements

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-2

7.2

Display elements

7200

Display elements

7-

Anzeige Legende 3x

Legend:

7.2.1

Display elements for device diagnostics

Display elements for device diagnostics

7-

Betrieb_Anzeige_Feldbus_PROFIBUS-DP_BA

LED on

LED flashes

LED off

LED

Meaning

POWER

Supply voltage is present

Supply voltage is not present

ONLINE

PNOZ mc3p online, data exchange is possible

Master has sent the telegram "Global Control Clear". Virtual input bits i0 ... i23 are set
to "0"; expanded input bits i24 ... i127 are frozen.

PNOZ mc3p not online

OFFLINE

PNOZ mc3p offline, data exchange is not possible

PNOZ mc3p not offline

FAULT

Application Watchdog Timeout

1 Hz

Configuration error, length of input and/or output data during initialisation of the
PNOZ mc3p does not match the configuration
Remedy:
Ensure that the right GSD file has been used.

2 Hz

Configuration error, length/contents of configuration data during initialisation of the
PNOZ mc3p does not match the configuration
Remedy:
Ensure that the right GSD file has been used.

4 Hz

Error when initialising PROFIBUS-DP

No error