Examples without position control

9

Application examples

9

9000

Application examples

Application examples

9-

9.1

Examples without position control

9100

Examples without position control

9-

Applikationsbeispiel_ohne_Lageregelung_PNOZms3_einleitung_Bit10_BA

Evaluation of bit: "Unfeasible or single-channel signal from the

incremental encoder", without position control

Diagnosticbit 10: "Unfeasible or single-channel signal from the incre-

mental encoder" must be evaluated in the user program during opera-

tion in such a way that a set bit leads to a safety-related error reaction

(shutdown).

9.1.1

Example 1

Example 1

9-

Applikationsbeispiel_ohne_Lageregelung_1_PNOZms3_sofort_absch_BA

Immediate shutdown as soon as diagnostic bit 10 is set.

The bit is evaluated as follows:

The connection point "Input Device OK" must be incorporated into the

application and evaluated in such a way that a shutdown occurs if the

connection point "Input Device OK"= 0.