beautypg.com

Overview, Unit structure, Scope of delivery – Pilz PNOZ mo5p 4 n/o burner User Manual

Page 9: Unit features, 2overview, 1 unit structure, 1 scope of delivery, 2 unit features

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

2-1

2.1

Unit structure

2

Overview

2

2000

Overview

Overview

2-

2.1

Unit structure

2100

Unit structure

2-

2.1.1

Scope of delivery

Scope of delivery

2-

Lieferumfang_Brck_774639_modul_BA

`

Expansion module PNOZ mo5p

`

Jumper 774 639

2.1.2

Unit features

Unit features

2-

Geraetemerkmale_Zusatz BA Einleitung

The product has the following features:

Gertemerkmale PNOZ mo5p

`

Can be configured in the PNOZmulti Configurator

`

Positive-guided relay outputs, diverse:

4 safety outputs

Depending on the application, up to PL e of EN ISO 13849-1 and up

to SIL CL 3 of EN IEC 62061

`

Suitable for controlling the safety valves on a burner in accordance

with EN 50156

`

Status indicators

`

Plug-in connection terminals (either cage clamp terminal or screw ter-

minal)

`

Max. 8 expansion modules and one fieldbus module can be connect-

ed to a base unit. A max. 6 of these may be the expansion modules

PNOZ mo5p, PNOZ mo4p, PNOZ mo2p and PNOZ mo1p.