Service life graph of output relays

8

Technical details

8.2

Service life graph of output relays

8200

Service life graph of output relays

8-

Lebensdauerkurve_Relais_Text vor Kurve

The service life graphs indicate the number of cycles from which failures

due to wear must be expected. The wear is mainly caused by the elec-

trical load; the mechanical load is negligible.

Lebensdauerkurve SIS_212

Lebensdauerkurve_Relais_Text nach Kurve_SIS212_SIR-SLR Bsp

Example

`

Inductive load: 0.2 A

`

Utilisation category: AC15

`

Contact service life: 1 000 000 cycles

Provided the application requires fewer than 1 000 000 cycles, the PFH

value (see technical details) can be used in the calculation.

To increase the service life, sufficient spark suppression must be provid-

ed on all output contacts. With capacitive loads, any power surges that

occur must be noted. With contactors, use freewheel diodes for spark

suppression.

Lebensdauerkurve_Relais_Text nach Kurve-2_ Empfehlung Halbleiterausgänge

We recommend you use semiconductor outputs to switch 24 VDC

loads.

10

1

10

100

1000

10000

0.1

DC1: 24 V

AC1: 230 V

DC13: 24 V

AC15: 230 V

D

Nennbetriebstr

om (A)

GB

Nominal operating current (A)

F

Courant coupé (A)

E

Corriente nominal de ser

vicio (A)

I

Corrente di eser

cizio nominale (A)

NL

Nominale bedrijfsstr

oom (A)

D Schaltspielzahl x 10

3

GB Cycles x 10

3

F

Nombre de manœuvres x 10

3

E

Número de ciclos x 10

3

I

Numero dei cicli di commutazione x 10

3

NL Aantal schakelingen x 10

3