8technical details, 1 technical details – Pilz PNOZ mo5p 4 n/o burner User Manual
Page 28
8.1
Technical details
8
Technical details
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-2
Technische Daten_Satz No.
No. stands for order number.
Si-Kennzahlen_alle
Si-Kennzahlen_Zusatz_Relais_1kan_EN954_Cat2
Requirement on 1-channel relay outputs for Cat. 2 in accordance with
EN 954-1: An additional output switches to a safe condition in the event
of an error or, if that is impossible, signals a hazardous condition.
Si-Kennzahlen_Zusatz_Relais_Lebensdauer_BA
The PFH value depends on the switching frequency and the load on the
relay output. If the service life graphs are not accessible, the stated PFH
value can be used irrespective of the switching frequency and the load,
as the PFH value already considers the relay's B10d value as well as the
failure rates of the other components.
Si_Kennzahlen_Erläuterung
All the units used within a safety function must be considered when cal-
culating the safety characteristic data.
Technische Daten_Satz Normen
The standards current on 2009-01 apply.
Cross section of external conductors with screw terminals
Power supply, inputs, auxiliary output, semiconductor out-
puts, test pulse outputs, cascading outputs:
2 core, same cross section, flexible:
Relay outputs:
1 core flexible
0.5 - 2.5 mm², 22 - 12 AWG
2 core, same cross section, flexible:
with crimp connectors, without insulating sleeve
0.50 - 1.25 mm², 22 - 16 AWG
without crimp connectors or with TWIN crimp connectors
0.50 - 1.25 mm², 22 - 16 AWG
Torque setting with screw terminals
0.40 - 0.50 Nm
Spring-loaded terminals: Terminal points per connection
1
Stripping length
9 mm
Dimensions
Height
94.0 mm
Width
22.5 mm
Depth
121.0 mm
Weight
170 g
Safety characteristic data
Unit
Operating mode
EN ISO 13849-1
PL
EN 954-1
Category
EN IEC 62061
SIL CL
PFH [1/h]
t
M
[year]
relay outputs
single-channel
PL c (Cat. 1)
Cat. 2
-
2.90E-08
20
relay outputs
dual-channel
PL e (Cat. 4)
Cat. 4
SIL CL 3
3.00E-10
20
CAUTION!
It is essential to consider the relay's service life graphs. The relay
outputs' safety-related characteristic data is only valid if the val-
ues in the service life graphs are met.
Mechanical data