beautypg.com

Pnozelog, Fault diagnostics – Pilz PNOZ e1p 24VDC 2so User Manual

Page 4

background image

PNOZelog

Fault diagnostics

1001137-EN-01-2008-03

Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany, Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

Decimal

error code

8,1

8, 2

8, 3

14, 13

2, 0, 0

2, 0, 1

2, 0, 2

2, 0, 3

Number of flashes

3x short - 8x long - 1x long - 3x short

3x short - 8x long - 2x long - 3x short

3x short - 8x long - 3x long - 3x short

3x short - 14x long - 13x long - 3x short

3x short - 2x long - 16x long - 16x long

- 3x short

3x short - 2x long - 16x long - 1x long

- 3x short

3x short - 2x long - 16x long - 2x long

- 3x short

3x short - 2x long - 16x long - 3x long

- 3x short

Description

Invalid operating mode

Supply interrupted, possibly caused by a short

to earth

U

B

<19.2 VDC

In the initialisation phase, short circuit between

the safety outputs and +24 VDC

U

B

<19.2 VDC

Remedy

Rectify wiring error at terminal S34, Y4, Y6 or Y7

Rectify wiring error at terminal A1 or check supply

voltage

Keep within the supply voltage range of 19.2 ... 30

VDC

Rectify wiring error at terminals 14, 24

Keep within the supply voltage range of 19.2 ... 30

VDC

Table 3: Error code, part 2