Pnozelog, Fault diagnostics – Pilz PNOZ e1p 24VDC 2so User Manual
Page 3

PNOZelog
1001137-EN-01-2008-03
Fault diagnostics
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany, Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
Decimal
error code
1
2
3
4
...
9
10
...
1, 0
1, 1
1, 9
10, 1
14, 5
1, 2
1, 3
1, 12
1, 13
1, 4
1, 5
1, 6
1, 7
1, 8
1, 11
1, 10
5, 10
Number of flashes
3x short - 1x long - 3x short
3x short - 2x long - 3x short
3x short - 3x long - 3x short
3x short - 4x long - 3x short
...
3x short - 9x long - 3x short
3x short - 10x long - 3x short
...
3x short - 1x long - 16x long - 3x short
3x short - 1x long - 1x long - 3x short
3x short - 1x long - 9x long - 3x short
3x short - 10x long - 1x long - 3x short
3x short - 14x long - 5x long - 3x short
3x short - 1x long - 2x long - 3x short
3x short - 1x long - 3x long - 3x short
3x short - 1x long - 12x long - 3x short
3x short - 1x long - 13x long - 3x short
3x short - 1x long - 4x long - 3x short
3x short - 1x long - 5x long - 3x short
3x short - 1x long - 6x long - 3x short
3x short - 1x long - 7x long - 3x short
3x short - 1x long - 8x long - 3x short
3x short - 1x long - 11x long - 3x short
3x short - 1x long - 10x long - 3x short
3x short - 5x long - 10x long - 3x short
Description
Faulty wiring, short circuit
Operating mode changed during operation
In the initialisation phase, short circuit between
the safety outputs and +24 VDC
During operation, short circuit between the
safety outputs and +24 VDC
During operation, short circuit between the
safety outputs and 0 VDC
or U
B
<19.2 VDC
Operating mode changed during operation
Unexpected status at S36
Wiring of operating mode “with detection of
shorts across contacts” faulty
1.) Feedback loop open
2.) PNOZ e6.1p, PNOZ e6vp: External feedback
loop closed, but internal feedback loop faulty
Open circuit
U
B
<19.2 VDC
Remedy
Rectify wiring error at terminals S34, S11-S14,
S21-S24, Y6 or Y4
Rectify wiring error at terminal Y4, Y6, Y7, Y37 or
S36
Rectify wiring error at terminals 14, 24
Rectify wiring error at terminals 14, 24
Rectify wiring error at terminals 14, 24;
Keep within the supply voltage range of 19.2 ... 30
VDC
Check wiring at terminals S23, Y6 or Y7
Check wiring at terminal S36
Rectify wiring error at terminal S12, S22 or S24
1.) Close feedback loop at terminal Y6 and Y7
2.) No remedy available to user - send unit to Pilz
Check the safety mat wiring
Keep within the supply voltage range of 19.2 ... 30
VDC
Table 3: Error code, part 1
Error codes
- PNOZ e1vp 10/24VDC 1so 1so t PNOZ e1vp 300/24VDC 1so 1so t PNOZ e1.1p 24VDC 2so PNOZ e3vp 10/24VDC 1so 1so t PNOZ e3vp 300/24VDC 1so 1so t PNOZ e3.1p 24VDC 2so PNOZ e5.11p 24VDC 2so PNOZ e5.13p 24VDC 2so PNOZ e6.1p 24VDC 4n/o 2so PNOZ e6vp 24VDC 4n/o 1so 1so t PNOZ e1p C 24VDC 2so PNOZ e1vp C 10/24VDC 1so 1so t PNOZ e1vp C 300/24VDC 1so 1so t PNOZ e1.1p C 24VDC 2so PNOZ e3vp C 10/24VDC 1so 1so t PNOZ e3vp C 300/24VDC 1so 1so t PNOZ e3.1p C 24VDC 2so PNOZ e5.11p C 24VDC 2so PNOZ e5.13p C 24VDC 2so PNOZ e6.1p C 24VDC 4n/o 2so PNOZ e6vp C 24VDC 4n/o 1so 1so t PNOZ e2.2p 24VDC 2so PNOZ e2.1p 24VDC 2so PNOZ e2.2p C 24VDC 2so PNOZ e2.1p C 24VDC 2so PNOZ e4.1p 24VDC 2so PNOZ e4vp 10/24VDC 1so 1so t PNOZ e4.1p C 24VDC 2so PNOZ e4vp C 10/24VDC 1so 1so t