32-Channel Analog Input Module

Module Data/Configuration Echo BTR

Module Data/Configuration Echo BTR

Module Data/Configuration Echo BTR

Module Data/Configuration Echo BTR

Module Data/Configuration Echo BTR

Word/Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

Diagnostic Data Byte

CE

HF

EE

CC

RT

IS

OR

PU

Diagnostics

1

16

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

Channel Fault

2

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

Channel Fault

3

16

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

Under Range

4

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

Under Range

5

16

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

Over Range

5

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

Over Range

7

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Sign

8

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

Sign

9

Channel 1 Data

Data

10

Channel 2 Data

Data

40

Channel 32 Data

Data

41

Channel 4

Channel 3

Channel 2

Channel 1

Type/Range

42

Channel 8

Channel 7

Channel 6

Channel 5

Type/Range

43

Channel 12

Channel 11

Channel 10

Channel 9

Type/Range

44

Channel 16

Channel 15

Channel 14

Channel 13

Type/Range

45

Channel 20

Channel 19

Channel 18

Channel 17

Type/Range

46

Channel 24

Channel 23

Channel 22

Channel 21

Type/Range

47

Channel 28

Channel 27

Channel 26

Channel 25

Type/Range

48

Channel 32

Channel 31

Channel 30

Channel 29

Type/Range

49

Channel 4

Channel 3

Channel 2

Channel 1

Data Format

50

Channel 8

Channel 7

Channel 6

Channel 5

Data Format

51

Channel 12

Channel 11

Channel 10

Channel 9

Data Format

52

Channel 16

Channel 15

Channel 14

Channel 13

Data Format

53

Channel 20

Channel 19

Channel 18

Channel 17

Data Format

54

Channel 24

Channel 23

Channel 22

Channel 21

Data Format

55

Channel 28

Channel 27

Channel 26

Channel 25

Data Format

56

Channel 32

Channel 31

Channel 30

Channel 29

Data Format

57

Chan 8

Chan 7

Chan 6

Chan 5

Chan 4

Chan 3

Chan 2

Chan 1

Filter Freq

58

Chan 16

Chan 15

Chan 14

Chan 13

Chan 12

Chan 11

Chan 10

Chan 9

Filter Freq

59

Chan 24

Chan 23

Chan 22

Chan 21

Chan 20

Chan 19

Chan 18

Chan 17

Filter Freq

60

Chan 32

Chan 31

Chan 30

Chan 29

Chan 28

Chan 27

Chan 26

Chan 25

Filter Freq

61

Automatic Calibration Rate

Autocal

62

Debug Flags

Debug Flags

63

Real Time Sampling

RTS

In differential mode every other channel is skipped. For example: Word 9 = Channel
1, Word 11 = Channel 2, Word 13 = Channel 3... The status bits are paired. For
example, Bit 0 and 1 in Word 4 (Under Range) will be associated with Channel 0.

Chapter Summary

In this chapter you learned the meaning of the status information that the input