beautypg.com

Spectrum Controls 1771sc-IFE32 User Manual

Page 20

background image

10 PLC-5

TM

32-Channel Analog Input Module

Input 1-
Input 2-

Input 3+
Input 4+

Common Group 1

Input 5-
Input 6-

Input 7+
Input 8+

Common Group 2

Input 9-

Input 10-

Input 11+

Input 12+

Common Group 3

Input 13-
Input 14-

Input 15+
Input 16+

Common Group 4

Input 1+
Input 2+
Input 3-
Input 4-
Common Group 1
Input 5+
Input 6+
Input 7-
Input 8-
Common Group 2
Input 9+
Input 10+
Input 11-
Input 12-
Common Group 3
Input 13+
Input 14+
Input 15-
Input 16-
Common Group 4

-

-

-

-

2-Wire

Transmitter

2-Wire

Transmitter

Power

Supply

Power

Supply

Source Ground

Connection Diagram for 16 Differential

Inputs and Two-wire Transmitters

All unsed inputs should have their + and - inputs tied together

and to Commons to reduce noise. Tie power supply grounds

together to minimize ground loops.

Attention: This signal must be between +14.5V and common voltage

otherwise channel-to-channel cross talk can cause invalid input

readings and invalid under or over range readings.

The sensor cable must be shielded. The shield must extend

the length of the cable to the point of termination.

+

+ +

+

Input 1-
Input 2-

Input 3+
Input 4+

Common Group 1

Input 5-
Input 6-

Input 7+
Input 8+

Common Group 2

Input 9-

Input 10-

Input 11+

Input 12+

Common Group 3

Input 13-
Input 14-

Input 15+
Input 16+

Common Group 4

Input 1+
Input 2+
Input 3-
Input 4-
Common Group 1
Input 5+
Input 6+
Input 7-
Input 8-
Common Group 2
Input 9+
Input 10+
Input 11-
Input 12-
Common Group 3
Input 13+
Input 14+
Input 15-
Input 16-
Common Group 4

+

-

+

-

Source Ground

Connection Diagram for 16 Differential

Inputs and Four-wire Transmitters

All unsed inputs should have their + and - inputs tied together

and to Commons to reduce noise. Tie power supply grounds

together to minimize ground loops.

Attention: This signal must be between +14.5V and common voltage

otherwise channel-to-channel cross talk can cause invalid input

readings and invalid under or over range readings.

The sensor cable must be shielded. The shield must extend

the length of the cable to the point of termination.

4-Wire

Transmitter

4-Wire

Transmitter

Power

Supply

Power

Supply