beautypg.com

Spectrum Controls 1771sc-IFE32 User Manual

Page 35

background image

Chapter 4: Configuring Your Module 25

max_scale = 1000

BCD

= 1000

16

If scaling is defined properly the min scale value is less than the max scale value
(scale

min

< scale

max

). If the min scale value is not less than the max scale value a

configuration fault is declared and scaling is not applied.

*If min = max = 0 then scaling is disabled. This is the default configuration.

Scale

Scale

Scale

Scale

Scale W

W

W

W

Wor

or

or

or

ord Configuration Bits

d Configuration Bits

d Configuration Bits

d Configuration Bits

d Configuration Bits

Word/Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Group

0

Channel 1 Min Scale

Min Scale

1

Channel 1 Max Scale

Max Scale

62

Channel 32 Min Scale

Min Scale

63

Channel 32 Max Scale

Max Scale

If differential mode is used every other channel scale group is skipped. For example,
when channel 1 is used in differential mode Scale Word 0 (Min Scale) and Word 1
(Max Scale) are used. Word 2 and Word 3 are skipped. Word 4 and Word 5 are Min
and Max Scale words for channel 2, etc.

Scaling:

*Default:

Min Scale Value (Binary)

0

Max Scale Value (Binary)

0

Important:

If scaling is selected for any channel, all channels must be scaled. If scaling is not
required on certain channels, set those to the default input range: 0 to 4095 for 0 to +
voltage or current ranges, and -4095 to +4095 for - to + voltage or current ranges.

If scaling is not selected, the module BTR file length will be 23.

Important: Use decimally addressed bit locations for PLC-5 processors.

The module will return values outside the scaling range. For example, if a module is in
the 0–5V dc mode, scaled for 0 to 5000, and has –2V dc applied, it will return –2000.

Default Configuration:

Default Configuration:

Default Configuration:

Default Configuration:

Default Configuration:

If a write block of five words, with all zeroes, is sent to the Analog Input Module (cat.
no. 1771sc-IFE32), default selections will be:

·

1 to 5V dc or 4 to 20mA (dependent on configuration jumper setting)

·

BCD data format

·

no real time sampling (RTS)