6 PLC-5

TM

32-Channel Analog Input Module

ATTENTION: Electrostatic discharge can degrade performance or cause permanent damage.
Handle the module as stated below.

Wear an approved wrist strap grounding device, or touch a grounded object to rid yourself of
electrostatic charge before handling the module.

Handle the module from the front, away from the backplane connector. Do not touch backplane
connector pins.

Keep the module in its static-shield bag when not in use.

WARNING: Power, input and output (I/O) wiring must be in accordance with Class I, Division 2
wiring methods (Article 501-4(b) of the National Electrical Code, NFPA 70) and in accordance
with the authority having jurisdiction.

Peripheral equipment must be suitable for the location in which it is used.

WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABLIITY FOR CLASS I, DIVISION 2

WARNING – EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER
BEFORE REPLACING OR WIRING MODULES.

WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS
BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, AND D OR
NON-HARZARDOUS LOCATIONS ONLY.

Power Requirements:

Your module receives its power through the 1771 I/O power supply. The module
requires a maximum of 400mA from the backplane.

Add this current to the requirements of all other modules in the I/O chassis to prevent
overloading the chassis backplane and/or backplane power supply.

!

!

!

!

!

!