beautypg.com

Spectrum Controls 1746sc-CTR4 User Manual

Page 56

background image

56

SLC 500

50 KHz Counter / Flowmeter Module

Module

Status LED

on.

Both Count and

Frequency

Modes Not

Working

Counter Mode is

not working.

Check K+M

Scaling Status

Bit 12

Check Counter Max,

Limit, and

Zero Flags.

Fault

Check Input

Signal Level.

Check Input

Range Setting

Config Bits 4+5.

Check External

Enable

Disconnect any

wires to enable.

Reset K+M

Scale Factors

Reset Flag Bit

Config. Reg Bit 2

Turn off

Stop on Limit

Stop on Zero

Bits

Frequency Mode

is not working.

Check Freq Max

Flag Status

Reg Bit 9

Reset F

Scale Factor

Reduce Input

Frequency

Check F Scaling

Status

Bit 13

Check Freq Zero

Flag Status

Reg Bit 11

Verfify Counter

is counting faster

than 1Hz.

...continued from

previous page.