3/24

NAMEPLATE AREA

SET SCREW

ANNUNCIATION PATH

EXTERNAL GROUND

PROVISION

Electrical Termination - 4-20 mA Output

Drawing

0091546

Formula for determining

maximum loop resistance

R

L

(MAX) = V

Supply

- 10V

20mA

NOTE: An external ground screw is included for additional
earth ground connection.

72” flying leads are provided for connection
to a terminal strip within a cabinet or a splice
within an outlet box:

Red (+)

Loop Voltage: 10 to 36 VDC

Black (–)

Output: 4 to 20 mA

Orange Switch

Contacts:

Yellow

Normally Open Solid-State Relay


Brown RS-485

(A)

White RS-485

(B)


Blue

(Used for 1-5 VDC Output)


Green Earth Ground


Bare

Drain Wire - Connected to

Earth Ground (trimmed at factory)

}

}

}

Horizontal Installation

The following figure depicts the proper horizontal installation profile; with the external

ground provision and set screw (annunciation path) oriented downward.

The nameplate (tag) should not cover the set screw.

Align the nameplate slot with the set

screw; i.e., the set

screw should be

visible in the

nameplate

slot.

Drawing