Factory modbus settings – SOR 815DT Smart User Manual

Page 19

background image

Form 1588 (09.14) ©SOR Inc.

19/24

Modbus

Register

Register Definition

Read/Write

"Data

Type"

Description

80

R

UINT8

BSL firmware version

84

R

UINT8

BSL firmware revision

88

R

UINT8

Firmware build

92

R

UINT8

Firmware version

96

R

UINT8

Firmware revision

100

R

UINT16

Sensor product ID

104

R

UINT16

Sensor model ID

108

R

UINT32

Sensor serial number

112

Device History

R

UINT32

Unit on time (seconds)

116

R

UINT32

Unit power ups

120

R

Float

Low pressure (PSI)

124

R

Float

High pressure (PSI)

128

R

Float

Low temperature (°C)

132

R

Float

High temperature (°C)

136

R

Float

Low loop voltage (V)

140

R

Float

High loop voltage (V)

144

R

UINT32

Status Flags

148

Set fixed output mode

R/W

Float

Percentage of span to write

152

Pressure point zero

R/W

Float

Pressure Point Zero

156

Pressure point span

R/W

Float

Pressure Point Span

160

Perform self test

W

n/a

Write only

Note:

All Modbus command data is sent and received as 4 bytes. For an eight-bit variable, the least
significant byte contains the value.

Factory Modbus Settings

The following summarizes the Modbus settings for the 815DT as shipped from the factory:

Slave

ID:

1

Baud

Rate:

19200

Data

Bits:

8

Parity:

Even

Stop

Bits:

1

Flow

Control:

None