Delta Electronics AC Motor Drive VFD-XXXM User Manual
Page 9
English-9
SUMMARY OF PARAMETER SETTINGS
a
: The parameter can be set during operation
Parameter
Explanation
Settings
Factory
Setting
Customer
a
Pr.00
Source of Frequency
Command
00: Master frequency determined by
digital keypad (LC-M02E)
01: Master frequency determined by 0 to
+10 V input on AVI terminal with
jumpers
02: Master frequency determined by 4 to
20mA input on ACI terminal with
jumpers
03: Master frequency determined by RS-
485 Communication port
04: Master frequency determined by
potentiometer on digital keypad
00
a
Pr.01
Source of Operation
command
00: Operation determined by digital
keypad
01: Operation determined by external
control terminals, keypad STOP is
effective
02: Operation determined by external
control terminals, keypad STOP is
ineffective
03: Operation determined by RS-485
communication port, keypad STOP is
effective
04: Operation determined by RS-485
communication port, keypad STOP is
ineffective
00
Pr.02 Stop
Method
00: Ramp stop
01: Coast Stop
00
Pr.03
Maximum Output
Frequency
50.00 to 400.0 Hz
60.00
Pr.04
Maximum Voltage
Frequency (Base
Frequency)
10.00 to 400.0Hz
60.00
Pr.05
Maximum Output
Voltage (Vmax)
115V/230V: 0.1 to 255.0V
460V: 0.1 to 510.0V
575V: 0.1 to 637.0V
220.0
440.0
575.0
Pr.06
Mid-point Frequency
0.10 to 400.0Hz
1.50
Pr.07 Mid-point
Voltage
115V/230V: 0.1 to 255.0V
460V: 0.1 to 510.0V
575V: 0.1 to 637.0V
10.0
20.0
26.1
Pr.08
Minimum Output Freq
0.10 to 20.00Hz
1.50
Pr.09
Minimum Output
Voltage
115V/230V: 0.1 to 255.0V
460V: 0.1 to 510.0V
575V: 0.1 to 637.0V
10.0
20.0
26.1
a
Pr.10
Acceleration Time 1
0.1 to 600.0 sec or 0.01 to 600.0 sec
10.0
a
Pr.11
Deceleration Time 1
0.1 to 600.0 sec or 0.01 to 600.0 sec
10.0
a
Pr.12
Acceleration Time 2
0.1 to 600.0 sec or 0.01 to 600.0 sec
10.0
a
Pr.13
Deceleration Time 2
0.1 to 600.0 sec or 0.01 to 600.0 sec
10.0
Pr.14
Accel S-curve
00 to 07
00
a
Pr.15
Jog Accel/Decel Time
0.1 to 600.0 sec or 0.01 to 600.0 sec
1.0