English-12

Parameter

Explanation

Settings

Factory

Setting

Customer

Pr.45





Pr.46

Multi-Function Output
Terminal 1
(Photocoupler output)



Multi-function Output
Terminal 2
(Relay Output)

00: AC Drive Operational
01: Maximum Output Frequency Attained
02: Zero Speed
03: Over-Torque Detection
04: Base-Block (B.B) Indication
05: Low Voltage Indication
06: AC Drive Operation Mode
07: Fault Indication
08: Desired Frequency Attained
09: PLC Program Running
10: PLC Program Step Completed
11: PLC Program Completed
12: PLC Operation Paused
13: Top Count Value Attained
14: Preliminary Counter Value Attained
15: Warning (PID feedback loss,

communication error)

16: Below the Desired Frequency
17: PID supervision
18: Over Voltage supervision
19: Over Heat supervision
20: Over Current stall supervision
21: Over Voltage stall supervision
22: Forward command
23: Reverse command
24: Zero Speed (Includes Drive Stop)

00





07

a

Pr.47

Desired Frequency
Attained

0.00 to 400.0 Hz

0.00

a

Pr.48

Adjust Bias of External
Input Frequency

0.00 to 200.0%

0.00

a

Pr.49

Potentiometer Bias
Polarity

00: Positive Bias
01: Negative Bias

00

a

Pr.50

Potentiometer
Frequency Gain

0.10 to 200.0%

100.0

Pr.51

Potentiometer Reverse
Motion Enable

00: Reverse Motion Disabled in negative

bias

01: Reverse Motion Enabled in negative

bias

00

a

Pr.52

Motor Rated Current

30.0% FLA to 120.0% FLA

FLA

a

Pr.53

Motor No-Load Current 00%FLA to 99%FLA

0.4*
FLA

a

Pr.54

Torque Compensation

00 to 10

00

a

Pr.55

Slip Compensation

0.00 to 10.00

0.00

Pr.56 Reserved

Pr.57

AC Drive Rated Current Display (unit: 0.1A)

##.#

Pr.58

Electronic Thermal
Overload Relay

00: Standard Motor (self cool motor)
01: Inverter Motor (auxiliary cool fan on

motor)

02: Inactive

02