Parameter

Explanation

Settings

Factory

Setting

Customer

a

Pr.59

Electronic Thermal
Motor Overload

30 to 300 sec

60

Pr.60

Over-Torque Detection
Mode

00: Over-Torque Detection Disable
01: Enabled during constant speed

operation until the allowable time for
detection (Pr.62) elapses.

02: Enabled during constant speed

operation and halted after detection.

03: Enabled during acceleration until the

allowable time for detection (Pr.62)
elapses.

04: Enabled during acceleration and

halted after detection.

00

Pr.61

Over-Torque Detection
Level

30 to 200 %

150

Pr.62

Over-Torque Detection
Time

0.0 to 10.0 seconds

0.1

Pr.63

Loss of ACI (4-20mA)

00: Decelerate to 0 Hz
01: Stop immediately and display "EF"
02: Continue operation by last frequency

command

00

a

Pr.64

User Defined Function
for Display

00: Display AC drive output Frequency

(Hz)

01: Display User-defined output

Frequency (H*Pr.65)

02: Output Voltage (E)
03: DC Bus Voltage (u_)
04: PV (i)
05: Display the value of internal counter

(c)

06: Display the setting frequency (F or

o=%)

07: Display the parameter setting (Pr.00)
08: Reserved
09: Output Current (A)
10: Display program operation (0.xxx),

Fwd, or Rev

06




a

Pr.65

Coefficient K

0.01 to 160.0

1.00

a

Pr.66

Communication
Frequency

0.00 to 400.0 Hz

0.00

Pr.67

Skip Frequency 1

0.00 to 400.0 Hz

0.00

Pr.68

Skip Frequency 2

0.00 to 400.0 Hz

0.00

Pr.69

Skip Frequency 3

0.00 to 400.0 Hz

0.00

Pr.70

Skip Frequency Band

0.00 to 20.00 Hz

0.00

01 to 15

The factory setting of VFD075M43A is 10.

15

Pr.71

PWM Carrier
Frequency

575V series: 01 to 10

6

Pr.72

Auto Restart Attempts
after Fault

00 to 10

00