Delta Electronics AC Motor Drive VFD-XXXM User Manual
Page 18

English-18
Parameter
Explanation
Settings
Factory
Setting
Customer
Pr.142
Second Source of
Frequency Command
00: Keypad Up/Down
01: AVI (0-10V)
02: ACI (4-20mA)
03: Communication
04: Keypad potentiometer
00
115V/230V 370-450 Vdc
380.0
460V
740-900 Vdc
760.0
Pr.143
Software Braking Level
575V 925-1075
Vdc
950.0
Pr.144
Total operation time
(Day)
Read Only
Pr.145
Total operation time
(Minutes)
Read Only
Pr.146 Line
start
Lockout
00: Disable
01: Enable
00
Pr.147
Decimal Number of
Accel / Decel Time
00: One decimal
01: Two decimals
00
Pr.148
Number of Motor Poles 02 to 20
04
Pr.149
Gear Ratio for Simple
Index Function
4 to 1000
200
Pr.150
Index Angle for Simple
Index Function
00.0 to 360.0
180.0
Pr.151
Deceleration Time for
Simple Index Function
0.00 to 100.00 sec
0.00
Pr.152
Skip Frequency Width
0.00 to 400.0Hz
0.00
Pr.153
Bias Frequency Width
0.00 to 400.0Hz
0.00
Pr.154 Reserved
a
Pr.155
Compensation
Coefficient for Motor
Instability
0.0: Disable
0.1 to 5.0 (recommended setting d2.0)
0.0
a
Pr.156
Communication
Response Delay Time
0 to 200 (x500us)
0
a
Pr.157
Communication Mode
Selection
0: Delta ASCII
1: Modbus
1