Delta Electronics AC Motor Drive VFD-XXXM User Manual
Page 10

English-10
Parameter
Explanation
Settings
Factory
Setting
Customer
a
Pr.16
Jog Frequency
0.00 to 400.0 Hz
6.00
a
Pr.17
1st Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.18
2nd Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.19
3rd Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.20
4th Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.21
5th Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.22
6th Step Speed Freq.
0.00 to 400.0Hz
0.00
a
Pr.23
7th Step Speed Freq.
0.00 to 400.0Hz
0.00
Pr.24
Reserve Operation
Inhibition
00: Enable REV operation
01: Disable REV operation
00
Pr.25
Over-Voltage Stall
Prevention
00: Disable
115V/230V: 330 to 450 Vdc
460V: 660 to 900 Vdc
575V: 825 to 1025 Vdc
390
780
975
Pr.26
Over-current Stall
Prevention during
Acceleration
00: Disable
20% to 200%
150
Pr.27
Over-current Stall
Prevention during
Operation
00: Disable
20% to 200%
150
Pr.28
DC Braking Current
Level
00 to 100 %
00
Pr.29
DC Braking during
Start-up
0.0 to 5.0 sec
0.0
Pr.30
DC Braking during
Stopping
0.0 to 25.0 sec
0.0
Pr.31
Start-point for DC
Braking
0.00 to 60.00 Hz
0.00
Pr.32
Momentary Power Loss
Operation Selection
00: Stop operation after momentary
power loss
01: Continues after momentary power
loss, speed search starts with Master
Frequency
02: Continues after momentary power
loss, speed search starts with
Minimum output Frequency
00
Pr.33
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec
2.0
Pr.34
Base-Block Time for
Speed Search
0.3 to 5.0 sec
0.5
Pr.35
Maximum Current
Level for Speed Search
30 to 200 %
150
Pr.36
Upper Bound of Output
Frequency
0.10 Hz to 400.0 Hz
400.0
Pr.37
Lower Bound of Output
Frequency
0.00 Hz to 400.0 Hz
0.00