beautypg.com

Delta Electronics AC Motor Drive VFD-XXXM User Manual

Page 10

background image

English-10

Parameter

Explanation

Settings

Factory

Setting

Customer

a

Pr.16

Jog Frequency

0.00 to 400.0 Hz

6.00

a

Pr.17

1st Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.18

2nd Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.19

3rd Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.20

4th Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.21

5th Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.22

6th Step Speed Freq.

0.00 to 400.0Hz

0.00

a

Pr.23

7th Step Speed Freq.

0.00 to 400.0Hz

0.00

Pr.24

Reserve Operation
Inhibition

00: Enable REV operation
01: Disable REV operation

00

Pr.25

Over-Voltage Stall
Prevention

00: Disable
115V/230V: 330 to 450 Vdc
460V: 660 to 900 Vdc
575V: 825 to 1025 Vdc

390
780
975

Pr.26

Over-current Stall
Prevention during
Acceleration

00: Disable
20% to 200%

150

Pr.27

Over-current Stall
Prevention during
Operation

00: Disable
20% to 200%

150

Pr.28

DC Braking Current
Level

00 to 100 %

00

Pr.29

DC Braking during
Start-up

0.0 to 5.0 sec

0.0

Pr.30

DC Braking during
Stopping

0.0 to 25.0 sec

0.0

Pr.31

Start-point for DC
Braking

0.00 to 60.00 Hz

0.00

Pr.32

Momentary Power Loss
Operation Selection

00: Stop operation after momentary

power loss

01: Continues after momentary power

loss, speed search starts with Master
Frequency

02: Continues after momentary power

loss, speed search starts with
Minimum output Frequency

00

Pr.33

Maximum Allowable
Power Loss Time

0.3 to 5.0 sec

2.0

Pr.34

Base-Block Time for
Speed Search

0.3 to 5.0 sec

0.5

Pr.35

Maximum Current
Level for Speed Search

30 to 200 %

150

Pr.36

Upper Bound of Output
Frequency

0.10 Hz to 400.0 Hz

400.0

Pr.37

Lower Bound of Output
Frequency

0.00 Hz to 400.0 Hz

0.00