Indramat SOT Interface

The Indramat SOT (serial operator terminal) is

sometimes used with CLM or DLC servo controls.
When it is used, the OmniLink OIT must connect to
the SOT instead of the CLM or DLC. Connections
to the Indramat SOT are as follows:

Table 2.14

Indramat SOT Connections

Link PN 106738

OmniLink
Feed Port

Function /
Color

Indramat SOT
Connector X3

Pin 1
(GND)

Ground
(WHITE)

Pin 7

Pin 2
(RXD)

Receive data
from feed
(BLACK)

Pin 2

Pin 3
(TXD)

Transmit data
to feed (RED)

Pin 3

Notes:

‚

For old communication board only, the
following Parameter Values must be set up at
the CLM or DLC:
a) A100 = 3.
b) B102 = 0.
c) B118 = 2 01 0.
d) B119 = 1920 8 1 02 OR

B119 = 1920 8 1 03 7 (Typical)

‚

For new communication board only, the
following Parameter Values must be set up at
the CLM or DLC:
a) B102 = 0.
b) B118 first number must not be 0.
c) B119 = 1920 8 1 02 OR

B119 = 1920 8 1 03 7 (Typical)

‚

The SOT should be connected to the CLM or
DLC as shown in the Indramat manuals. Once
the SOT operation is verified, serial port 2 must
be configured and “Relay Mode” must be
enabled for the OmniLink 5000 to pass
commands to the CLM or DLC through the
SOT.
a) Press and simultaneously.
b) Enter the password “SOT” when prompted.
c) Select “SOT Parameters” from the menu.
d) Select “Configure Port 2" from the menu.
e) Set baud rate to 9600, parity to None, data

bits to 8, and stop bits to 1.

f) Go back to the first menu (the on with “SOT

parameters”).

g) Select “Enable Relay Mode”.