41

Create your own resource files with your UNVTs, UCPTs, and user

functional profiles.

Automatically generate Neuron C code that implements your device

interface.

Edit your Neuron C code to implement your device functionality.

Compile and build your application, and download it to an Echelon

Evaluation Board, Control Module, or to your own devices.

Test with prototype hardware to test your device’s I/O and related

hardware.

Install your device into a L

ON

W

ORKS

network and test your device

interoperating with other L

ON

W

ORKS

devices.

Use the LNS Plug-in Framework to develop an LNS plug-in for your

device.

Test your LNS plug-in with the LonMaker Integration Tool to ensure that

your device is easy to configure and install.

The NodeBuilder FX Development Tool (Service Release 1 or later) is required to

build applications for Series 5000 devices.
For more information about using the NodeBuilder FX Development Tool, see the

NodeBuilder FX/FT Quick Start and the NodeBuilder FX User’s Guide.
The NodeBuilder FX Development Tool uses device template files to represent

target device hardware configuration information. The NodeBuilder Device

Template wizard runs during the creation of a new device template. This wizard

provides an opportunity to select predefined hardware templates. At a later

point in the development process, you can access the hardware template through

the Development and Release folders of the project pane.
After you create the hardware template, drag the new hardware template to the

device. Drag the newly created icon in the User Templates folder to the Release

folder of the device template to complete the procedure.
You can update the user-defined hardware template at any time by double-

clicking the template icon. Your new changes affect any projects opened and

compiled using this template. A Build All might be required if you change a

hardware template without making any other changes.
The following sections describe how to configure the development environment

for Neuron 3150 Control Modules and FT 5000 Control Modules.

Configuration for FT 5000 Control Modules

The NodeBuilder FX Development Tool, Service Release 1 (4.01), does not include

hardware templates for the FT 5000 Control Module. However, a future release

of the NodeBuilder FX Development Tool will include appropriate hardware

templates for the FT 5000 Control Module.
You can use the FT 5000 Evaluation Board hardware template as a base for

creating a custom hardware template for the FT 5000 Control Module. Table 15

on page 42 shows the values required for each tab in the NodeBuilder device

template editor to support an FT 5000 Control Module. Use this hardware

template as a basis for your device development.