Performance characteristics and cabling, Free topology tp/ft-10 and tp/ft-10f – Echelon LonWorks Twisted Pair Control Module User Manual
Page 28
![background image](/manuals/735715/28/background.png)
20
Network Cabling and Connection
Performance Characteristics and Cabling
For performance characteristics and cabling information, refer to the sources of
information shown in summary Table 9. The specifications shown in Table 9
are provided for convenience only and are not intended to be comprehensive.
Table 9. Module Performance Summary
Module
Cable Distance
Number of
Nodes
Information Sources
FT 5000,
TP/FT-10,
TP/FT-10F
Bus: 2700 m (8850 feet)
worst case with Belden
®
85102 cable
Free topology: 500 m
(1640 feet) worst case
with Belden 85102 cable
and with no repeaters
(1000 m [3280 ft] total
wire with one repeater)
64 at -40 to +85 °C • Series 5000 Chip Data
Book (005-0199-01)
•
FTT-10 User's Guide (078-
0114-01)
•
FTT-10A User's Guide
(078-0156-01)
•
LPT-10 User's Guide (078-
0105-01)
•
Control Module Data
Sheet (003-0121-01)
TP/XF-78,
TP/XF-78F
Bus: 1400 m (4600 feet)
worst case with 3 m (10
feet) stubs with 22
AWG (0.65 mm) Level
IV Cable
64 at 0 to +70 °C
44 at -40 to +85 °C
•
TPT User's Guide (078-
0025-01)
•
Control Module Data
Sheet (003-0121-01)
TP/XF-1250
Bus: 130 m (430 feet)
worst case with 0.3 m (1
foot) stubs with 22
AWG (0.65 mm) Level
IV Cable, or Category 5
or 6 cable
64 at 0 to +70 °C
32 at -20 to +85 °C
16 at -40 to +85 °C
Control Module Data Sheet
(003-0121-01)
Notes:
1. Worst case distance figures are based on variations in device distribution,
device temperature, device voltage, wire characteristics, and FT 5000
Smart Transceiver or Neuron Chip characteristics, and allow for an
average wire temperature of up to +55 °C.
2. Network length for TP/FT-10 channel varies by wire type.
Free Topology TP/FT-10 and TP/FT-10F
The following sections describe the wire characteristics and cabling terminations
for Free Topology TP/FT-10 channels. The FT 5000 Control Module and the
Neuron 3150 TP/FT-10 and TP/FT-10F Control Modules use a Free Topology
TP/FT-10 channel.